Honeywell Switch C6097A User Manual

C6097A,B  
Pressure Switches  
PRODUCT DATA  
FEATURES  
• For use with natural gas, liquid propane (LP) gas,  
or air.  
• Diaphragm-actuated safety-limit switch.  
• Switch can be wired to turn on alarm.  
• C6097A models break control circuit at setpoint  
on pressure fall.  
• C6097B models break control circuit at setpoint  
on pressure rise.  
• Lockout with manual reset and recycle options.  
• Lockout models have external manual reset  
button.  
• Removable transparent cover protects scaleplate  
and adjusting knob.  
• Pipe tappings allow selection of positive  
pressure, differential pressure (air only) or  
venting connections (NPT mount only).  
• 1/4 in. NPT or flange mount models for direct  
mounting to Honeywell Integrated Valve Train.  
APPLICATION  
• Optional switch position indicator lamp available.  
• IP54 enclosure standard.  
The C6097 Pressure Switches are safety devices used in  
positive-pressure or differential-pressure systems to sense  
gas or air pressure changes.  
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in.  
wc or 1.5 to 7 psi.  
• Surge orifice.  
Contents  
CP-UM-5109E  
® U.S. Registered Trademark  
Copyright © 2000 Honeywell Inc. • All Rights Reserved  
65- 0237- 1  
 
   
C6097A,B PRESSURE SWITCHES  
Table 1. Pressure Switch Model Selection.  
Manual Reset  
Differential  
Non-Manual Reset  
Differential  
Maximum  
Maximum Maximum  
Rated  
Pressure  
Operating  
at  
at  
Switch  
Pressure Minimum Maximum  
Range Setpoint Setpoint  
Differential (continuous) Manual  
Action at  
Setpoint  
Model  
Nominal Maximum  
Type  
(psi)  
Reset  
Mediaa  
Comments  
C6097A1004 0.4 to 5 in.  
wc  
0.16 in.  
wc  
0.24 in. wc Additive  
2.9  
No  
Air/Gas Breaks N.O. 1/4 in. NPT  
to C.  
Mount  
connection  
on pressure  
fall.  
C6097A1012 3 to 21 in. 2.4 in. wc  
wc  
4.2 in. wc  
4.2 in. wc  
12 in. wc  
12 in. wc  
4.3  
Yes  
Yes  
Yes  
Yes  
No  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
1/4 in. NPT  
Mount  
C6097A1020 3 to 21 in. 2.4 in. wc  
wc  
4.3  
Flange Mount  
C6097A1038 12 to 60  
in. wc  
10 in. wc  
4.8  
1/4 in. NPT  
Mount  
C6097A1046 12 to 60  
in. wc  
10 in. wc  
4.8  
Flange Mount  
C6097A1053 3 to 21 in.  
wc  
0.24 in.  
wc  
0.48 in. wc  
0.48 in. wc  
4.3  
1/4 in. NPT  
Mount  
C6097A1061 3 to 21 in.  
wc  
0.24 in.  
wc  
4.3  
No  
Flange Mount  
C6097A1079 12 to 60  
in. wc  
1.1 in. wc 2.4 in. wc  
4.8  
No  
1/4 in. NPT  
Mount  
C6097A1087 12 to 60  
in. wc  
1.1 in. wc 2.4 in. wc  
4.8  
No  
Flange Mount  
C6097A1095 0.4 to 5 in. 0.6 in. wc  
wc  
1.0 in. wc  
1.4 psi  
1.4 psi  
2.9  
Yes  
Yes  
Yes  
No  
1/4 in. NPT  
Mount  
C6097A1103 1.5 to 7  
psi  
1.1 psi  
1.1 psi  
9.3  
Flange Mount  
14 in. NPT Mount  
Flange Mount  
C6097A1111  
1.5 to 7  
psi  
9.3  
C6097A1129 1.5 to 7  
psi  
0.1 psi  
0.1 psi  
0.3  
9.3  
C6097A1137 1.5 to 7  
psi  
0.3  
9.3  
No  
1/4 in. NPT  
Mount  
C6097A1210 0.4 to 5 in.  
wc  
0.16 in.  
wc  
0.24 in. wc  
2.9  
No  
Flange Mount  
C6097A1228 0.4 to 5 in.  
wc  
2.9  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Flange Mount  
C6097B1002 12 to 60  
in. wc  
10 in. wc  
10 in. wc  
12 in. wc  
12 in. wc  
4.2 in. wc  
4.2 in. wc  
1.4 psi  
1.4 psi  
Subtractive 4.8  
Air/Gas Breaks N.C. 1/4 in. NPT  
to C.  
Mount  
connection  
on pressure  
rise.  
C6097B1010 12 to 60  
in. wc  
4.8  
4.3  
4.3  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Air/Gas  
Flange Mount  
C6097B1028 3 to 21 in. 2.4 in. wc  
wc  
1/4 in. NPT  
Mount  
C6097B1036 3 to 21 in. 2.4 in. wc  
wc  
Flange Mount  
C6097B1044 1.5 to 7  
psi  
1.1 psi  
1.1 psi  
21.0  
Flange Mount  
C6097B1051 1.5 to 7  
psi  
21.0  
4.3  
1/4 in. NPT  
Mount  
C6097B1069 3 to 21 in.  
wc  
0.24 in.  
wc  
0.48 in. wc  
Flange Mount  
C6097B1077 12 to 60  
in. wc  
1.1 in. wc 2.4 in. wc  
4.8  
No  
Flange Mount  
C6097B1085 12 to 60  
in. wc  
1.1 in. wc 2.4 in. wc  
4.8  
No  
1/4 in. NPT  
Mount  
C6097B1093 1.5 to 7  
psi  
0.1 psi  
0.1 psi  
0.3 psi  
21.0  
21.0  
4.3  
No  
Flange Mount  
C6097B1101 1.5 to 7  
psi  
0.3 psi  
No  
1/4 in. NPT  
Mount  
C6097B1119 3 to 21 in.  
wc  
0.24 in.  
wc  
0.48 in. wc  
No  
1/4 in. NPT  
Mount  
a Acceptable media: Natural gas, liquid propane (LP) gas, and air  
.
3
65-0237—1  
 
C6097A,B PRESSURE SWITCHES  
Table 2. Switch Ratings (Amperes)  
120/240 Vac, 50/60 Hz  
When Installing this Product...  
1.  
Read these instructions carefully. Failure to follow them  
can damage the product or cause a hazardous  
condition.  
Inductive  
Resistive  
Full Load  
3.0  
Locked Rotor  
18.0  
5.0  
2.  
Check the ratings given in the instructions and on the  
product to make sure that the product is suitable for  
your application.  
3.  
4.  
Installer must be a trained, experienced service  
technician.  
After installation is completed, check out product  
operation as provided in these instructions.  
Table 3. Alternate Electrical Ratings when used with  
Honeywell Flame Safeguard Programmers.  
Device  
Rating  
Ignition Transformer 540 VA  
Pilot Valve  
Main Valve  
50 VA  
WARNING  
400 VA with 2-1/2 times inrush.  
Electrical Shock Hazard.  
Can cause serious personal injury or death.  
Disconnect power supply before beginning installation.  
More than one disconnection can be involved.  
27/32 (22) HOLE  
2-21/32 (68)  
2-1/4  
(57)  
Mounting  
1-1/4  
(32)  
NOTE: On flange models, remove the label holding the  
O-ring in place and make sure O-ring seal is in place  
before mounting the pressure switch on the valve.  
2-23/32 (69)  
5/8 (16)  
1/32  
(1)  
The C6097 models allow NPT or flange (directly to valve)  
mounting. The NPT models have a hexagonal fitting with a  
1/4 in. NPT tapping, which is the high pressure connection, in  
differential applications. The bleed fitting is 1/8 in. NPT  
tapped. In differential pressure control applications using air  
only, connect the lower pressure to the bleed fitting. See Fig. 1  
and Table 1. In applications using combustible gases, vent the  
bleed tapping according to applicable standard code or  
jurisdictional authority.  
2-23/32 (69)  
INDICATOR  
PRESSURE INLET  
2
(52)  
C6097 models with flange mount can be fitted directly to  
Honeywell Integrated Valve Train (model specific). See Fig. 2  
and Table 1. The flange mount models vent internally, with no  
external tap.  
2 (52)  
TERMINAL DIAGRAM  
1
2
3
NO  
NC  
Mount the C6097A,B in any position.  
COM  
M17124  
P
Leak Check  
After installation, perform a leak check on the pressure switch:  
Fig. 2. C6097 Flange Mount dimensions in in. (mm).  
1.  
2.  
Turn on main gas. Make sure gas has reached the  
pressure switch (e.g., high gas pressure switch)  
Check installation for gas leaks using a gas leak  
detector or a soap solution.  
INSTALLATION  
WARNING  
Explosion or Fire Hazard.  
Can cause severe personal injury, death or  
property damage.  
Observe all safety requirements each time a control is  
installed on a burner.  
65-0237—1  
4
 
 
C6097A,B PRESSURE SWITCHES  
WIRING  
WARNING  
Electrical Shock Hazard.  
Can cause serious personal injury or death.  
Disconnect power supply before beginning installation.  
More than one disconnection can be involved.  
Make sure that all wiring agrees with all applicable local  
codes, ordinances and regulations. An opening is provided to  
accommodate rigid conduit or armored cable for line voltage  
operation (see Fig. 3 and 4). Do not overload the switch  
contacts (see Switch Ratings in the Specifications section).  
The switching schematic is shown in Fig. 5.  
Fig. 4. C6097 (recycle model) with cover removed.  
SETTINGS AND ADJUSTMENTS  
Pressure Setpoint Adjustment  
To adjust the pressure setting, turn the setpoint adjustment  
dial (Fig. 3, 4 and 5) clockwise  
pressure setting and counterclockwise  
pressure setting.  
to increase the  
to decrease the  
NO  
2
Fig. 3. C6097 (manual reset switch model)  
with cover removed.  
NC  
C
1
C6097A BREAKS C-NO, MAKES C-NC ON PRESSURE  
FALL. MANUAL RESET MODELS LOCK OUT.  
1
2
C6097B BREAKS C-NC, MAKES C-NO ON  
PRESSURE RISE AND LOCKS OUT.  
M17123  
Fig. 5. C6097 schematic.  
5
65-0237—1  
 
   
C6097A,B PRESSURE SWITCHES  
OPERATION AND CHECKOUT  
Operation  
Checkout  
The manual reset C6097A diaphragm actuates the snap-  
acting switch to break a control circuit and lock out when  
pressure falls to the scale setting. The recycle C6097A  
models recycle automatically when the control circuit returns  
to scale setting plus differential.  
C6097 Gas Fuel Application  
1.  
2.  
Set cutoff pressure.  
Open main supply line. Depress reset lever on lockout  
models until switch makes control circuit.  
Set controller and limit switch to call for heat.  
For C6097A: Close the manual gas shutoff valve.  
C6097 should open control circuit when pressure  
reaches cutoff point.  
3.  
4.  
The manual reset C6097B diaphragm actuates the snap-  
acting switch that breaks a control circuit and locks out when  
the pressure rises to the scale setting. The recycle C6097B  
models recycle automatically when the control pressure falls  
to the scale setting minus differential.  
For C6097B: Open the manual gas shutoff valve, wait a  
few minutes for the pressure to rise; then lower the  
scale setting until the switch breaks control circuit and  
locks out.  
For C6097A: Open the shutoff valve, return the  
pressure switch to its original setting and press the reset  
button (if necessary).  
For C6097B: raise setting to normal and press reset  
button (if necessary).  
Allow system to operate through at least one complete  
cycle to make sure all components are functioning  
properly.  
Manual Resetting  
5.  
6.  
The C6097A manual reset models lock out when pressure  
falls to the scale setting and require manual resetting after the  
pressure rises to scale setting plus differential to resume  
normal operation.  
The C6097B manual reset models lock out when pressure  
rises to the scale setting and require manual resetting after  
the pressure falls to scale setting minus the differential to  
resume normal operation.  
C6097A Air Application  
To reset, once normal operating pressure is restored, push the  
reset button in as far as it goes, then release.  
1.  
2.  
3.  
Set cutoff pressure.  
Turn on fan.  
Block fan inlet or filter area. Switch should break control  
circuit when pressure drops to cutoff point. Manual reset  
models lock out.  
Remove obstruction. Press reset lever (manual reset  
models) and allow system to operate through at least  
one complete cycle to be sure all components are  
functioning properly.  
IMPORTANT  
Lockout models cannot be made to recycle  
automatically by permanently holding in the reset  
lever.  
4.  
65-0237—1  
6
 
 
7
65-0237—1  
 
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis, MN 55408-0524  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
Honeywell Asia Pacific Inc.  
Room 3213-3225  
Sun Hung Kai Centre  
No. 30 Harbour Road  
Wanchai  
M2H 3N7  
Hong Kong  
Honeywell Latin American Region  
480 Sawgrass Corporate Parkway  
Suite 200  
Honeywell Europe S.A.  
3 Avenue du Bourget  
1140 Brussels  
Sunrise FL 33325  
Belgium  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
65-0237—1 G.R. Rev. 4-00  
 

Grundig MP3 Player 30GB User Manual
HannsG Computer Monitor HG 171DPB User Manual
Harbor Freight Tools Air Compressor 67853 User Manual
Harman Kardon Turntable CDR 26 User Manual
Hasbro Games 59917 User Manual
Honeywell Smoke Alarm 5808W3 User Manual
HP Hewlett Packard Personal Computer 8000F User Manual
HP Hewlett Packard Server DL185 User Manual
HTC Cell Phone RAPH500 User Manual
Hunter Fan Air Cleaner 30240 User Manual